Télécharger la fiche technique PDF
TVN V152 Vanne à Passage Direct Tige Montante est un type de vanne à passage direct qui est capable de suivre la position d’ouverture/fermeture en déplaçant le mouvement de la tige de haut en bas, est capable de suivre électroniquement le mouvement en ajoutant une clé de surveillance, et la position d’ouverture complète ne perturbe pas le débit. Le Vanne à Passage Direct Tige Montante génère une faible perte de charge selon les vannes papillon
Application Range
- Potable water applications
- Waste water
- Water treatment and distribution systems
- Mining industry
- Shipbuilding and drilling facilities
- HVAC systems
Related Products
- V991 Surface Box
- V993 Extension Spindle
- V851 Y-Strainer
- V301 Air Release Valve
- V201 Swing Check Valve
Rising Stem Gate Valve Product Features
- GGG40/50 Ductile Iron Body & Disc allows high impact and streching resistance
- With Full Bore design, ensures minimized pressure loss and increased energy efficiency
- Maintenance free valve design
- Fully EPDM vulcanised wedge maintains full stop of flow and can absorb smaller particules in the flow. (NBR coated wedge is optional)
- Stainless steel stem with threads for high strength
- Maintenance-free and corrosion-resistant multi stem O-rings ensures higher durability
- Brass wedge nut provides fixation of the stem and low torques.
- With isolated bonnet nuts, no risk of corrosion
- Bidirectional use. Possible to install on horizontal and vertical pipelines with varied flow directions
- Fixed wedge structures prevents vibration
- With precise machined stem, ensures low torque requirements during operation
- Full coating on the body and disc internally & externally with an average of 250 microns. Higher coating thicknesses are available when required.
- WRAS approved coating available upon request which meets hygienic requirements for potable water applications
- For big size valves, balanced positioned lifting holes on the body ease transportation and installation
- Suitable for vacuum conditions
- Suitable for shut-off and isolation purposes. Not suitable for regulation purposes
- Electrical actuator connection is done with an intermediate top flange arrangement
- Suitable to use with above-underground applications. Can be operated with handwheel, gearbox, actuator and spindle
- Hydrostatic test pressure for seat: PN x 1.1 , for shell: PN x 1.5 according to EN 12266-1.